Current Revision posted to RAM | STAAD | OpenTower Wiki by Seth Guthrie on 10/23/2020 9:22:37 PM
 Product(s):RAM Elements
 Version(s):Any
 Environment: N/A
 Area: Design
 Original Author:Bentley Technical Support Group

For additional information see Ram Elements - Tilt Up Wall [FAQ]

How is Tilt-up wall design checked in ACI 318-14?

According to section 11.4.1.3 Slenderness effects shall be calculated in accordance with 6.6.4, 6.7 or 6.8. Alternatively, out-of-plane slenderness analysis shall be permitted using 11.8 for walls meeting the requirements of that section. 

Ram Elements Tilt-up wall module only checks slenderness effects using Section 11.8 - Alternative method for out-of-plane slender wall analysis, and consequently any walls that do not meet the requirements of 11.8.1.1 will have warnings in the output. For example: 

“The wall must be tension controlled, Section 11.8.1.1b” - Where there is too much compression the tension strain is limited and this warning can occur..

 “Insufficient reinforcement to resist cracking moment, Section 11.8.1.1c” - This indicates that Mcr > phi Mn. Additional reinforcement or larger bars should resolve this.

 “Excessive vertical stress, Section 11.8.1.1d” - This indicates that Pu>0.06f’cAg which cannot easily be resolved other than making the wall thicker (assuming the Pu is correct).

Tilt-up walls can also be checked as shear walls.

Alternatively the wall can be evaluated as a Concrete Wall using the Concrete Wall Module rather than the Tilt-up wall module. 

See Also

Ram Elements - Tilt Up Wall [FAQ]

[[Tilt-up wall analysis error for inactive DOF]]

RAM Elements Masonry Wall FAQ

Tags: RAM Elements, tilt-up wall, concrete wall